UNITEST INSTRUMENTS

Your Test & Measurement Specialists

PHONE: (08) 9248 8601   Email: This email address is being protected from spambots. You need JavaScript enabled to view it.

HV Diagnostics HVA200 VLF Test Set

b2-hva200
b2-hva200b2-hva200-nahaufnahmeb2-hva200-transportb2-hva200-steuerungseinheit

Building on the worldwide success of the HVA series of VLF test sets, the HVA200 takes our tried and trusted design principles on to the next level.      For the first time, we are able to offer VLF output voltages up to 200kV peak (138kV rms), allowing the user to perform voltage withstand tests on assets with network voltages as high as 132kV.

Brand: HV Diagnostics InternationalHV Diagnostics International

Specifications

b2-hva200.pdf

 

VLF & DC
Sinusoidal VLF output voltage up to 200 kV (138 kV rms)
DC (±) voltages up to 200 kV
TD & PD
upgradeable with Tan Delta & Partial Discharge Diagnostics
Smallest & lightest test set available
850 kg but powerful - max. capacitance 6 µF
No limited operating time. 
Run the system for many hours.
Easy transport!
Transportation and mounted solutions
Flexible positioning!
V-type position for a space saving configuration (laboratory set-up)
 
 
  • Pure sinusoidal output voltage (load-independent)
  • Output current 140 mA max.
  • Cable Testing According IEEE400
  • Interface: Optical fibre & USB
  • PC software “b2 Suite®” with various control and reporting functions included
  • RMS digital metering of voltage and current.
    Automatic measurement of R and C
  • Automatic load calculation and frequency
    selection (0.01 - 0.1 Hz)
  • Load independent, true symmetrical sinusoidal output over the entire power range
  • Hybrid System
 

Being far more compact, lighter and lower cost than any other withstand testing solution at this voltage level, the launch of the HVA200 puts the opportunity to bring this level of testing capability in-house into reach for more asset owners and contractors than ever before.

As with the rest of the HVA series, the HVA200 may optionally include a module for performing highly sensitive cable diagnostics alongside the withstand test.

Our symmetrical, load-independent true sine wave output voltage wave shape makes repeatable Tan Delta (TD) measurements possible, allowing the global health of the cable insulation to be assessed, whilst our user-friendly offline Partial Discharge (PD) mapping module allows minor insulation defects or jointing errors to be detected and located before they lead to premature cable failure.

  • Testing 132KV systems or DC to 200KV
  • Cable testing
  • HV transformers, motors. infrastructure



Vivax Metrotech